TR-102323R1 (Revision1) : Guidelines for Electromagnetic Interference Testing In Power Plants
MIL-STD-461(D/E)


Guidelines for Electromagnetic Interference / Susceptibility Testing in Power Plants

Classification Applicable
Frequency
Test Limit Related
Test Standards
Emission Conducted 30kHz-50kHz
Picture 7-1 MIL-STD-461D,CE101
Conducted 50kHz-400kHz Picture 7-2 MIL-STD-461D,CE102
Radiated M-Field 30Hz-100kHz Picture 7-3 MIL-STD-461D,RE101
E-Field 10kHz-1GHz Picture 7-4 MIL-STD-461D,RE102
Suscepti-bility Continuous Wave 10kHz-1GHz
10V/m
MIL-STD-462D,RS103
30Hz-50kHz 6.3Vrms avg. MIL-STD-461D,CS101
Continuous Wave Low Frequency 103dBuA avg. MIL-STD-461D,CS114
Conducted 50kHz-400kHz
7Vrms,avg MIL-STD-461C CS02
High Frequency
Transients 1.2/50us,Open Ckt กพ3kV MIL-STD-462D,CS116
Surges 8/20us,Short Ckt
High Frequency,
Infrequent
Transients Impulse
& Bursts of IMPULSE
Low Energy,Frequent
5/50ns Bulk Current:กพ60A peakVoltage:กพ3kV
at 50งู
MIL-STD-462D,CS115
ESD 1/30 ns Air:กพ15kV
Contact:กพ8Kv
IEC801-2


For any questions, please contact us