Home > Request Test > Power Plan EMC |
|
Untitled Document
|
|

|
 |
TR-102323R1 (Revision1) : Guidelines for Electromagnetic Interference Testing In Power Plants
MIL-STD-461(D/E) |
 |
Guidelines for Electromagnetic Interference / Susceptibility Testing in Power Plants |
|
| Classification |
Applicable
Frequency |
Test Limit |
Related
Test Standards |
| Emission |
Conducted |
30kHz-50kHz |
Picture 7-1 |
MIL-STD-461D,CE101 |
| Conducted |
50kHz-400kHz |
Picture 7-2 |
MIL-STD-461D,CE102 |
| Radiated |
M-Field |
30Hz-100kHz |
Picture 7-3 |
MIL-STD-461D,RE101 |
| E-Field |
10kHz-1GHz |
Picture 7-4 |
MIL-STD-461D,RE102 |
| Suscepti-bility |
Continuous Wave |
10kHz-1GHz |
10V/m |
MIL-STD-462D,RS103 |
| 30Hz-50kHz |
6.3Vrms avg. |
MIL-STD-461D,CS101 |
| Continuous Wave |
Low Frequency |
103dBuA avg. |
MIL-STD-461D,CS114 |
| Conducted |
50kHz-400kHz |
7Vrms,avg |
MIL-STD-461C CS02 |
| High Frequency |
| Transients |
1.2/50us,Open Ckt |
กพ3kV |
MIL-STD-462D,CS116 |
| Surges |
8/20us,Short Ckt |
High Frequency,
Infrequent |
Transients Impulse & Bursts
of IMPULSE
Low Energy,Frequent |
5/50ns |
Bulk Current:กพ60A peakVoltage:กพ3kV
at 50งู |
MIL-STD-462D,CS115 |
| ESD |
1/30 ns |
Air:กพ15kV
Contact:กพ8Kv |
IEC801-2 |
|
|
|
|
|
|
|